The embedded network specialist
+31-40-2301.922

CAN-CR220, High isolation CAN Repeater

ISO 11898-2 CAN Repeater with 4 kV galvanic isolation

The CAN-CR220 is used for the galvanic isolation of two segments of a CAN bus network and offers a very high galvanic isolation of 4 kV, allowing it be utilized in medical applications. One special feature of the Repeater is the automatic recognition and separation of a defective segment from the rest of the network so that the remaining network can continue working. After elimination of the defect, the segment is switched into the network again.
Ixxat CAN-CR220
Ixxat CAN-CR220
Ixxat CAN-CR220

The galvanic isolation isolates the CAN bus segments from each other as well as from the power supply.
The CAN-CR220 is tested according DIN/EN 50178 (DIN VDE 0160: 1988-05 and DIN VDE 0160/A1: 1989-04).

Features and benefits

  • Line protection up to 4 kV
  • Increased system reliability
  • Almost no influence on real-time behavior
  • Cost savings due to simple wiring
Technical data
Display Transmit and defective segment (two duo LEDs), Power (one LED)
CAN bus interface ISO 11898-2 with CAN choke. Two Sub-D9 connectors. CAN termination resistors are integrated (switchable).
Baudrate Up to 888 kbps
Delay 200 ns (corresponds ~40 m (~120ft.) bus length)
Power supply 9-32 V DC, 1.5 W typ., through terminals
Galvanic isolation CAN 1, CAN 2 and power supply are galvanic isolated against each other.
   
  Isolation voltage 1.01.0067.44400
  - 2,5 kV AC / 1 Min.
  - 3,5 kV AC / 1 Sec.
  - 4,0 kV DC / 1 Sec.
   
  Isolation voltage 1.01.0067.44300
  - 3,0 kV AC / 3 Min.
  - 3,75 kV AC / 1 Min.
  - 4,0 kV AC / 1 Sec.
Contents of delivery
- CAN-CR220
- Quick Reference Manual

Part number(s)

1.01.0067.44400
CAN-CR220, 2x CAN with 4kV Galvanic Isolation
CAN-CR220, 2x CAN with 4kV Galvanic Isolation
1.01.0067.44300
CAN-CR220, 2x CAN with 3kV Galvanic Isolation
CAN-CR220, 2x CAN with 3kV Galvanic Isolation

Getting interested?

Are you interested in the CAN-CR220, High isolation CAN Repeater? Please request, without any obligation, for a quote. Would you like more information? Please send an email to or visit our contact page.
You can call us if you like, we can be reached at +31-40-2301.922. We are pleased to help you and do offer you practical advice and support.

Related products

  • CAN-CR200

    Modular ISO 11898-2 CAN Repeater with backbone bus

  • CAN-CR100

    CAN / CAN FD repeater with screw terminals

  • CAN-CR120/HV

    CAN / CAN FD repeater with screw terminals and 3 kV galvanic isolation

  • CAN-CR300

    CAN / CAN FD repeater with screw terminals and 4 channels

PC CAN-interfaces
CAN Bridges & Gateways
Communicator CAN
CANopen X-gateway
CANopen PLC-extentions
canAnalyser 3 Suite
CAN Diagnostic Tools
CANopen Software
CAN Accessories